| Equipment Model |
HSBA11K-300-50 |
| Environmental Conditions | Working Environment | -0~+50 ℃ |
| Storage Temperature | -20~+70 ℃ |
| Relative Humidity | ≤90%RH, no condensation |
| Cooling Method | Forced air cooling, intelligent speed regulation |
| Altitude | 2000m, derating use above 2000m |
| Atmospheric Pressure | 79kPa~106kPa |
| Auxiliary Power Supply | Supply Voltage | 220Vac (-10%~+20% rated operation) |
| User Side Parameters | System | Single-phase |
| Rated Voltage | 220Vac |
| Voltage Range | Load mode: 50~300Vac Source mode: 50~300Vac |
| Current Range | 0.1~50A |
| Frequency Range | Load mode: 45~65Hz Resolution: 0.01Hz Source mode: 40~70Hz Resolution: 0.01Hz |
| Power Factor | ±0.5~±1.0 1: resistive load 0.5~1: simulated capacitive load, current leading -0.5~-1: simulated inductive load, current lagging |
| THDi | ≤3% @35%~100%load power |
| THDu | ≤1% @10%~100%power source power |
| Current Accuracy | 0.3% F.S (load) |
| Voltage Accuracy | 0.1% F.S (Power mode) |
| Setting Resolution | 0.01 V/A |
| Power Supply Regulation Rate | 0.05% F.S @10% change |
| Load Regulation Rate | 0.05% F.S |
| Response Time | ≤2s (10%-90% load change) |
| Working Modes | Load mode: constant current, constant power, constant resistance Source mode: bidirectional constant voltage |
| Grid-connected Side Parameters | Voltage Range | 90Vac~264Vac (power is limited by current limit during low-voltage feedback) |
| Frequency Range | 45~65Hz (adaptive to 50/60Hz power grid) |
| Maximum Grid-connected Current | 42A |
| Power Factor | ≥0.97 @20%~50%output power, nominal input voltage and frequency ≥0.99 @50%~100%output power, nominal input voltage and frequency |
| Maximum Static Voltage Withstood When Not Working | 600Vac |
| Protection Functions | Inverter | AC over/undervoltage, DC bus over/undervoltage, over/underfrequency, AC overcurrent, overtemperature, fan fault, etc. |
| Other Parameters | Noise | ≤65dB |
| Protection Grade | IP20 (single module) |
| Communication Function | Standard RS485 (external communication) |
| Start-up Time | Time delay from AC power-on to module output ≤10s |
| Efficiency | ≥92%, @220V, 100%load current, rated voltage condition |
| Standby Power Consumption | 16.5W (rated input voltage) |
| Volume | 480*443*89mm |
| Weight | ≤18kg |
| Safety Characteristics | Leakage Current | Leakage current ≤4.0mA |
| EMC Characteristic Standards | EN IEC 61000-3-2:2019/A1:2021 EN 61000-3-3:2013/A1:2019/A2:2021 |
| Insulation Resistance | Insulation resistance between DC part, AC part and shell, and between AC part and DC part ≥10MΩ |
| Insulation Strength | Terminal to shell: 2500V 60S, no breakdown and arcing Terminal to terminal: 2500V 60S, no breakdown and arcing Terminal to RS485: 2500V 60S, no breakdown and arcing RS485 to shell: 2500V 60S, no breakdown and arcing |