| Equipment Model |
HSBT20K-120-400 |
| Environmental Conditions | Operating Environment | -10~+60 ℃ |
| Storage Temperature | -40~+70 ℃ |
| Relative Humidity | ≤95%RH, no condensation |
| Cooling Method | Forced air cooling, intelligent speed regulation |
| Altitude | 2000m, derating required above 2000m |
| Atmospheric Pressure | 79kPa~106kPa |
| AC Side Parameters | Input System | Three-phase + PE |
| Rated Voltage | 380Vac |
| Input Current | ≤41A |
| Voltage Range | 323Vac~456Vac(-15%~+20%) |
| Frequency Range | 47~63Hz (adaptive to 50/60Hz power grid) |
| Power Factor | ≥0.97 @20%~50% output power, nominal input voltage and frequency ≥0.99 @50%~100% output power, nominal input voltage and frequency |
| THDi | ≤5% at full load |
| Maximum Static Voltage Withstood When Not Working | 460Vac |
| DC Side Parameters | Rated Voltage Range | 2~120Vdc |
| Voltage Range | 2-120Vdc |
| Current Range | -400A~400A |
| Rated Power | 20kW |
| Voltage Accuracy | 0.03%Fs |
| Current Accuracy | 0.05%Fs |
| Voltage Ripple Vpp | <1% F.S. |
| Current Ripple Ipp | <1A F.S |
| Voltage Ripple Vrms | 0.1% F.S. |
| Current Ripple Irms | <0.1% F.S. |
| Load Regulation | ≤±0.1% |
| Line Regulation | ≤±0.1% |
| Startup Overshoot | ≤5% |
| Operating Modes | Load Mode: Constant Current, Constant Voltage, Constant Power, Constant Resistance Source Mode: Constant Voltage Bidirectional Current Source |
| Current Rise Time | ≤2ms |
| Forward/Reverse Current Conversion Time | ≤20ms, seamless switching |
| Protection Functions | Inverter | AC over/undervoltage, DC bus over/undervoltage, over/underfrequency, AC overcurrent, AC current imbalance, overtemperature, fan fault, etc. |
| DC/DC | Over/undervoltage protection, overcurrent protection, overtemperature protection, short circuit protection, reverse connection protection, etc. |
| Other Parameters | Noise | ≤65dB |
| Protection Grade | IP20 (single module) |
| Communication Function | Standard external communication: RS485, internal communication: 485, CAN |
| Startup Time | Time delay from AC power-on to module output ≤10s |
| Efficiency | ≥92%@50V,400A |
| Auxiliary Power Supply | 230VAC±15% or 380VAC±15% |
| Standby Power Consumption | <10W |
| Volume | 2U |
| Weight | ≤30kg |
| Safety Characteristics | Safety Specification Standards | IEC 61010-1:2010 IEC 61010-1:2010/AMD1:2016 |
| EMC Characteristic Standards | EN IEC61000-6-2:2019 EN IEC61000-6-4:2019 |
| Leakage Current | Leakage current ≤3.5mA |